Type Of Installation
1 |
Routine Check sub-clause 2.1.4
2 |
Maximum peroid between inspections & testing as necessary
3 |
| General Installations |
|
|
| Domestic |
------- |
Change of tenancy/10 years |
| Commercial |
1 Year |
Change of tenancy/5 years |
| Educational Establishments |
4 months |
5 Years |
| Hospitals |
1 Year |
5 Years |
| Industrial |
1 Year |
3 Years |
| Residential Accommodation |
At change of occupancy/1 Year |
5 Years |
| Offices |
1 Year |
5 Years |
| Shops |
1 Year |
5 Years |
| Laboratories |
1 Year |
5 Years |
| |
|
|
| Buildings Open To The Public |
|
|
| Cinemas |
4 Months |
1 Year |
| Church Installations |
1 Year |
5 Years |
| Leisure Complexes |
4 Months |
1 Year |
| Places of Public Entertainment |
4 Months |
1 Year |
| Restaurants & Hotels |
1 Year |
5 Years |
| Theatres |
4 Months |
1 Years |
| Public Houses |
1 Year |
5 Years |
| Village Halls/Community Centres |
1 Year |
5 Years |
| |
|
|
| External Installations |
|
|
| Agricultural & Horicultural |
1 Year |
3 Years |
| Caravans |
1 Year |
3 Years |
| Caravan Parks |
6 Months |
1 Year |
| Highway Power Supplies |
As Convenient |
6 Years |
| Marinas |
4 Months |
1 Year |
| Fish Farms |
4 Months |
1 Year |
| |
|
|
| Special Installations |
|
|
| Emergency Lighting |
Daily/ Monthly |
3 Years |
| Fire Alarms |
Daily/ Monthly/Weekly |
1 Year |
| Launderettes |
1 Year |
1 Year |
| Petrol Filling Stations |
1 Year |
1 Year |
| Construction Site Installations |
3 Months |
3 Months |